The selection of water supply patterns in domestic water supply system of high-rise building

Wei Fu Sheng
Faculty of Urban Construction
ChongQing JianZhu University, China

ABSTRACT: Thorough the analysis and comparison of kinds of water supply patterns in domestic water supply system of high-rise building, it demonstrated that according to specific circumstances the selection of decompression means from water storage cistern or combined pattern of several water supply means ig more economical and reasonable nowadays.
KEYWORDS: high-rise building water supply patterns decompression means of water supply

The selection of water supply patterns is the key of designing water supply system of high. rise building, it concerns directly to the usage and cost of water supply system of the project. Usually, the pressure on the water main can not ensure an adequate domestic water supply to upper part of multi-storey building, in most cases, the zoned water supply pattern is used, ie, the lower part water supplied directly from the main, the upper part water supplied from boosted system.
As far as the current situation of urban water supply system interiorly concerned, the Pressure on the water main usually can supply water inside the building up to a height of 5-6 floor, thus other methods associated with the specific circumstances should be provided for the Water services of the upper part of the building. It is stated at 2.3.4 in The Design Norm of Building Water System (GBJ15-88)( it is shortly named as The Norm below)": the vertical zone to domestic water supply system of high-rise building should be relied reasonably on the terms such as usage requirement, performance of material or equipment, manage or maintenance, height of the building etc, also the pressure on the water main should be involved.
It is necessary to limite the static pressure on the lowest draw-off points of any vertical zone. To residential building, hotel, hospital, it must be limited to 300-350Kpa,while to office building, it must be limited to 350-450Kpa." Therefore, on the basis of the static press value of the vertical) zone according to the Norm, associated with the water supply pattern of building fire system, it is reasonable that the domestic water supply system of the upper part of the multi-toreys building must be zoned vertically.
There are basically three patterns for the high Part of the building in common use:1)Water supplied directly from the high-level water cisterns; 2)water supplied directly from the frequency converter pump; 3)from the auto-pneumatic system.
There‘s another statement at 7.4.7 in the The Design Norm of Building Fire System" If the supply authority‘s main with high pressure employed, there is no need for the high-level firing water storage cistern, if the boosted system employed, then the high-level cistern is necessary......".At present, the high-level firing water storage cistern is widely employed in a multi-storey building for the reason that the authority‘s main often can not satisfy the required pressure, and the temporary boosted system often be used.
It is commercial and easy to manage if the domestic and firing water stored together in the high-level cistern while the efficient volume of the cistern won‘t increase much. The cistern can keep the pressure stable, keep the balance of the pressure for cold and hot water supply system, in order to provide comfortable washing and shower.
The use of the frequency converter pump is limited interiorly for the reason that 1)only the pump cannot store any volumn of firing water; 2) the problem that supply water with minor or zero rate of flow exsists, 3) the frequency converter costs too much.
The dominating disadvantage of the auto-pneumatic system is the regulated volumn of the pneumatic-cylinder can‘t offer enough storage of firing water. The auto-pneumatic system is
widely used as two aspects: 1) to be regularly boosted equipment in a fire control system; 2)to be boosted equipment only for the highest several floors in a domestic water supply system in multi-storey buildings. As far as all above concerned, the pattetn of supplying water directly from the high-level cistern is widely spread in most of the multi-storey buildings in despite of the shortcomings that additional strutural loading on the building and the drinking water of the cistern might be polluted.
The pattern of water supply directly from cisterns can divided into several kinds according to The Norm, that is supply water by decompression from the high-level cistern or supply in parallel from the cisterns, or supply in serial from the cisterns, even the combination of several water supply patterns being adopted based on the specific circumstance.
There are two means of decompression pattern---- by break pressure storage cistem or by pressure reducing valve. The disadvantage of break pressure cistern is 1 )the cistern will make up certain surface of the floor. 2)the chances that the drinking water being polluted will increase, 3)the noise. With a view to the pressure reducing valve, the cost may be a litter high, but the area of the floor will be occupied much less, the problems of the pollution and the noise will not exist either, on the other hand, the quality and capability of the pressure-reducing valve inland is much better than before. There for, more and more pressure-reducing valve is used in tall buildings these days.
The pattern of supply water by decompression from the high-level storage cistern can be considered in practice as below:
1 The height of the building is about 50m
The water of the upper stroeys can supply from storage tank-pump--high level cistern-draw-off points. The water of the lower stroeys can supply directly from the mains. If the reliability of water supply is necessary, a vertical pipeline directly from the high-level storage cistern can be connected to the conduit of the lower part. A electric valve and a pressure- reducing valve are necessary on the vertical pipe, the electric valve shuts up at peacetime, the valve opens when the water mains cannot supply water properly. Fig. 1 shows the water supply pattern of the building around 50m. Reliability is the outstanding characteristic of this pattern. The pattern is widely used for another reason that it can take full advantage of the water main and the energe can be saved to some degree.
2 The height of the building is between 50-80m
The water of the upper stroeys can supply from storage tank-pump--high level cistern-pressure-reducing valve--draw-off points or from the cisterns in parallel. Fig.2 shows the decompression pattern. Fig.3 shows the parallel pattern.
Every zone of parallel water supply pattern is a separate system. The advantage of parallel pattern is the reliability of the system, easy to maintenance as the pumps being gathered together and subsequent operation costs are relatively small. The disadvantage of it is two sets of pumps and cisterns being necessary, this would enlarge the area being occupied by the equipments which would increase the cost accordingly. This shortcoming is most notable to the building in big cities.
The system of the decompression water supply pattern is simple and easy to manage, the facilities cost less and the area being occupied less as well. But the reliability of decompression system is not as good as parallel pattern. the cost of power is also high. Even so, the zoned decompression water supply pattern from high-level cistern has superiority because the condition of power supply is much better than before inland, the fee of power can be acceptable now. Commonly the high stroeys be zoned into two parts which is widely spreaded in the tall buildings. The Surgery Building of NO. 1 hospital of ChongQing Medical University designed by ChongQing Jianzhu University is an example. The total floorage of the building is 37756m2, there are 2 storeys below the ground, 23 storeys above the ground, the height of the building is 89. 1m. The zoned domestic water supply system is adopted in the case. There are two zone for the building-the upper and the lower. Water of the lower (4 storey below) supplied directly from the water mains, water of the upper (5 storey above) supplied from the storage tank-pump---high level cistern-pressure-reducing valve-draw-off points.

3 The height of the building is between 80-110m
The zoned and decompression pattern from high-level cistern is the recommended means of water supply for the upper part of the tall buildings, that is the pattern from the storage tank-pump---high level cistern-pressure-reducing valve-draw-off points, as show in Fig.4.
The parallel pattern of water supply from the cisterns is another recommended means. There are three minor vertical zones in the upper zone in the case.
4 The height of the building is beyond 110m
The seriat water supply pattern must be employed to avoid excessive high of the lift of the pump for the upper zone and excessive long of the pipeline to convey water. (Intermediate relay pump is necessary if there is no intermediate cisterns).
The combination means of the serial water supply pattern front high-level cistern and the
decompression pattern is recommended in the case. That is:
storage tank-pump--intermediate cistern--pump-high-level-cistern-pressure-reducing valve
Supply water in Decompression pattern Each zone
-draw-off points
as show in Fig.5. There will be one or several intermediate cisterns, three or more zones in the upper part.

1-water meter 2-storage tank 3-pump for domestic water 4-pressure-reducing valve 5-high-level cistern 6-electric valve

The characteristic of serial water supply pattern from high-level cistern is the pumps for the water source of the upper zone. It is applicable to super high buildings. No high---lifting pump and high-pressure pipeline are the notable advantages of the system. The disadvantages are;1)not convenient for management since the equipments being separated; 2)shock and sound proof being needed because the pumps being placed on the floor; 3)reliability is not enough in respect that supplying water of the upper-storeys enslaved to the lower.
The combination of the serial and decompressure pattern of water supply is widely used in the high-rise buildings for the reason that equipments (pumps and cisterns) can be reduced which will result in the costing less, convenient to maintenance, less shock and sound.
There are exceptions of course. ChongQing Yangtze Holiday Inn is an example. The height of the building is 79.65m. There are 1 storey below the ground and 23 storeys above the ground. Water supply of the lowest three storeys is the combination of the pump-cistern system, while water between 21-23 storeys supply from auto-pneumatic system. The static pressure of the lowest draw-off point of the lower part is about 0.8Mpa, for the reason that the prssure resistance of the material and the equipment being pretty good and a series of measures to proof the shock and sound being adopted accordingly.
To sum up, some ingredients must be consided in the selection of the water supply pattern in high-rise buildings. When the height of the building is about 50m, water of the lower zone supplys directly from water mains, to the upper zone, water supplys with the combination of the pump-cistern system; when the height is between 50-80m, the water of the upper storeys "supplys with the decompression pattern from the high-level cistern; when the height of is beyond 110m, the water of the upper storeys supplys with the combination of the serial pattern of the high-level cisterns and decompression means. In brief, The selection of the water supply pattern must rely on The Norm, associated with the specific circumstance of the very region and the specific condition of the project to ensure the economical and reasonable water supply pattern being adopted.

REFERENCE

1,< The Design Norm of Building Water System> (OBJI5-88) The Project Publishing House of China, Beijing, 1997
2,<Water engineering for high-rise buildings>The Publishing House of ChongQing University, ChongQing, 1996.
3,Discuss in Designing the high-level cistern of high-rise buildings, Wei Fushen, Journal of ChongQing JianZhu University, V20, n5, 1998

論文搜索

發(fā)表時(shí)間

月熱點(diǎn)論文

論文投稿

很多時(shí)候您的文章總是無緣變成鉛字。研究做到關(guān)鍵時(shí),試驗(yàn)有了起色時(shí),是不是想和同行探討一下,工作中有了心得,您是不是很想與人分享,那么不要只是默默工作了,寫下來吧!投稿時(shí),請(qǐng)以附件形式發(fā)至 paper@h2o-china.com ,請(qǐng)注明論文投稿。一旦采用,我們會(huì)為您增加100枚金幣。

成人福利视频在线观看_国产精品日韩久久久久_欧美全黄视频_欧美网色网址
一区二区三区欧美| 亚洲高清久久久| 亚洲精品写真福利| 免播放器亚洲一区| 一本久久a久久免费精品不卡| 91精品国产综合久久精品app| 国产精品久线观看视频| 视频一区中文字幕国产| av亚洲精华国产精华| 日韩精品资源二区在线| 亚洲精品成人a在线观看| 国产高清精品久久久久| 制服丝袜中文字幕一区| 亚洲欧美日韩国产成人精品影院| 国内国产精品久久| 欧美美女一区二区三区| 亚洲欧美日韩电影| 成人av免费网站| 久久久久99精品国产片| 日韩精品视频网| 91成人免费在线| 中文字幕一区二区三区在线不卡| 精品一区二区三区香蕉蜜桃| 欧美二区乱c少妇| 日韩精品一区二区三区在线观看 | 亚洲女女做受ⅹxx高潮| 国产精品一区二区黑丝| 日韩视频一区二区三区在线播放 | 婷婷成人综合网| 色视频一区二区| 中文字幕一区二区三区色视频| 国产一区二区在线看| 欧美一二三四在线| 丝袜诱惑制服诱惑色一区在线观看| 色综合天天狠狠| 国产精品国产馆在线真实露脸| 国产一区二区三区电影在线观看| 欧美一区午夜精品| 午夜精品影院在线观看| 欧美亚洲国产一区二区三区| 亚洲精品国产a| 色婷婷狠狠综合| 欧美一区二区观看视频| 久久久久久久久一| 日韩成人免费电影| 欧美性大战久久久久久久蜜臀| 中文字幕免费一区| 国产福利一区二区三区| 精品福利二区三区| 美女被吸乳得到大胸91| 日韩视频在线永久播放| 日本三级韩国三级欧美三级| 欧美福利电影网| 日韩成人一级大片| 日韩欧美一级在线播放| 久久精品国产亚洲a| 日韩欧美你懂的| 麻豆精品在线看| 亚洲综合成人在线| 91在线视频播放| 国产精品久久免费看| 成人黄色一级视频| 国产精品第五页| 99精品视频在线免费观看| 亚洲欧洲综合另类在线| 在线一区二区三区做爰视频网站| 亚洲综合一二区| 欧美日韩国产成人在线91| 日韩成人精品在线观看| 欧美日免费三级在线| 国产女同互慰高潮91漫画| 国产 日韩 欧美大片| 国产精品久久久久桃色tv| 91片在线免费观看| 亚洲精品一二三区| 欧美日韩免费电影| 日韩国产高清影视| 精品电影一区二区| 成人午夜视频在线| 亚洲主播在线播放| 日韩亚洲欧美成人一区| 国产乱子轮精品视频| 国产精品久久久久久久久免费桃花| 99re66热这里只有精品3直播| 亚洲一区二区视频| 日韩女优av电影| 高清国产一区二区| 一区二区三区精品| 日韩欧美在线一区二区三区| 国产高清不卡一区二区| 依依成人精品视频| 日韩一级成人av| 成人综合婷婷国产精品久久 | 亚洲美女精品一区| 777久久久精品| 国产成人在线免费| 一区二区三区高清在线| 日韩精品综合一本久道在线视频| 粉嫩久久99精品久久久久久夜| 伊人婷婷欧美激情| 欧美成人video| 99re成人精品视频| 蜜臀av性久久久久蜜臀aⅴ流畅 | 日韩av一区二区三区四区| 久久久精品国产免大香伊| 欧洲中文字幕精品| 精品一区二区三区日韩| 日韩毛片在线免费观看| 欧美一区二区三区人| 成av人片一区二区| 日韩精品每日更新| 亚洲欧洲精品成人久久奇米网| 91精品国产欧美一区二区成人| 国产成人丝袜美腿| 午夜精彩视频在线观看不卡| 国产免费久久精品| 欧美精品123区| www.成人网.com| 麻豆久久久久久| 亚洲激情一二三区| 国产亚洲人成网站| 在线91免费看| 91啪亚洲精品| 国产精品一区专区| 亚洲成人av资源| 国产精品久久久久久亚洲毛片| 欧美一区二区三区不卡| 色女孩综合影院| 国产成人av一区二区三区在线 | 91麻豆精品秘密| 国产一区免费电影| 日本三级韩国三级欧美三级| 亚洲女与黑人做爰| 久久久亚洲高清| 7777精品伊人久久久大香线蕉超级流畅 | 欧美精选在线播放| 91蜜桃在线免费视频| 一区二区三区欧美在线观看| 精品久久99ma| 欧美午夜精品久久久久久孕妇 | 国产成人亚洲精品狼色在线| 亚洲国产精品综合小说图片区| 中文字幕精品一区二区精品绿巨人| 日韩三级在线观看| 欧美午夜免费电影| 99久久国产综合色|国产精品| 国产精品一区一区| 免费国产亚洲视频| 丝袜诱惑制服诱惑色一区在线观看| 中文字幕日韩精品一区 | 亚洲一区二区三区四区的| 中文成人综合网| 久久久噜噜噜久久人人看| 91麻豆精品91久久久久久清纯 | 亚洲视频中文字幕| 国产亚洲污的网站| 成人晚上爱看视频| 亚洲精品国产一区二区精华液| 欧美精品久久99久久在免费线| 最新不卡av在线| 精品处破学生在线二十三| 欧美精品精品一区| 欧美主播一区二区三区美女| 国产成人鲁色资源国产91色综| 美女任你摸久久| 五月激情综合婷婷| 亚洲自拍另类综合| 一区二区三区日韩精品| 亚洲精品自拍动漫在线| 中文字幕在线一区| 国产精品热久久久久夜色精品三区| 26uuu亚洲综合色欧美| www国产精品av| 久久亚区不卡日本| 26uuu国产在线精品一区二区| 日韩美一区二区三区| 91精品国产入口在线| 337p亚洲精品色噜噜| 91精品国产高清一区二区三区蜜臀| 欧美喷水一区二区| 91麻豆精品国产91久久久使用方法 | 91玉足脚交白嫩脚丫在线播放| 99久久免费国产| 91小宝寻花一区二区三区| 91免费国产在线| 亚洲一区日韩精品中文字幕| 国产精品区一区二区三区| 国产视频一区二区三区在线观看| 国产三级精品视频| 日本一区二区视频在线观看| 亚洲国产高清在线观看视频| 国产精品美女久久福利网站| 1024成人网| 亚洲综合一区二区精品导航| 亚洲图片欧美综合| 日韩一区精品字幕| 青青草国产成人99久久| 韩国欧美国产1区| 成人一区在线看| 色综合久久精品|